Part Number:

MVS08N4NW6V

Range EasyPact
product name MVS08N
Device short name MVS08N
Product or component type Circuit breaker
Device application Distribution
Poles description 4P
Protected poles description 4P 4d
Neutral position Left
[In] rated current 800 A at 40 °C
network type AC
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code N
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category B
Trip unit name ETV6G
Trip unit technology Electronic
Trip unit rating 800 A
Complementary
Network frequency 50/60 Hz
Control type Electrically operated
Mounting mode Drawout
Mounting support Rail
Base plate
Connection position Vertical
Horizontal
Location of connection Rear
[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2
Circuit breaker CT rating 800 A
Breaking capacity 50 kA Icu at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 50 kA (Ics) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 20000 cycles (with maintenance) conforming to IEC 60947-2
10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Connection pitch 115 mm without spreader
Contact position indicator Yes
[Icm] rated short-circuit making capacity 105 kA (Icm) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current 50 kA (1 s) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Neutral protection setting Without protection (3D)
0.5 x Ir (3D + N/2)
1 x Ir (4D)
Trip unit protection functions LSIG
Protection type Short time short-circuit protection
Overload protection (long time)
Earth fault
Instantaneous short-circuit protection
Fault indication Internal fault
Overload
Short-circuit
Earth fault
Long time pick-up adjustment type Ir Adjustable 9 settings
Long time pick-up adjustment range 0.4…1 x In
Long time delay adjustment type Adjustable 9 settings
[tr] long-time delay adjustment range 0.5…24 s at 6 x Ir
Short-time pick-up adjustment type Isd Adjustable 9 settings
[Isd] short-time pick-up adjustment range 1.5…10 x Ir
Short-time delay adjustment type Adjustable 5 settings
[tsd] short-time delay adjustment range 100…400 ms
Instantaneous pick-up adjustment type Ii Adjustable 9 settings
Instantaneous pick-up adjustment range 2…15 x In
Off
Ground-fault pick-up adjustment type Adjustable 9 settings
Ground-fault time delay adjustment type -tg Adjustable 5 settings
[tg] ground-fault time delay adjustment range 100…400 ms
[Ig] ground-fault pick-up adjustment range 0.2…1 x In
Zone selective interlocking ZSI With
Display type Digital display
Type of measurement Voltage
Current sensor rating range 400/2000 A
Maximum breaking time 25 ms
Maximum closing response time 70 ms
Height 439 mm
Width 556 mm
Depth 395 mm
Net weight 85 kg
Environment
Standards IEC 60947-2
Product certifications CCC
IEC
CCS
GOST
Pollution degree 4 conforming to IEC 60664-1
IP degree of protection IP40
Ambient air temperature for operation -5…70 °C
Ambient air temperature for storage -40…85 °C without control unit
-25…85 °C with control unit