Part Number:

33350

This is a Compact NS1250N circuit breaker basic frame, 1250A, 50kA at 415 VAC 50/60 Hz, 3 poles . It is adapted for withdrawable devices manually operated, and it is an optimum choice for all standard applications. This basic frame is compatible with any type of trip unit which has to be ordered separately. It can be equipped with a variety of optional functions and accessories. The dimensions are 327mm (W) x 210mm (H) x 147mm (D). It ensures compliance with international standards (IEC 60947), CCC, EAC and marine specifications.

Specification:

Main
Range ComPact
Range of product ComPact NS630b…1600
Device short name Compact NS1250N
Product or component type Basic frame
Device application Distribution
Number of poles 3P
[In] rated current 1250 A at 50 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN/IEC 60947-2
Utilisation category Category B
[Icu] rated ultimate short-circuit breaking capacity 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Performance level N 50 kA 415 V AC
control type Rotary handle
Toggle
Mounting mode Drawout
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
[Icw] rated short-time withstand current 19.2 kA 1 s conforming to IEC 60947-2
Integral instant protection 40 kA
Mechanical durability 10000 cycles conforming to IEC 60947-2
Electrical durability 2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
3000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
4000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
5000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Power losses 84 W
Mounting support Backplate
Connection pitch 70 mm
Protection type Without protection
Height (H) 327 mm
Width (W) 210 mm
Depth (D) 147 mm
Environment
Standards IEC 60947-2
Product certifications ASEFA
ASTA
LCIE
Pollution degree 3 conforming to IEC 60947
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to EN 50102
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -50…85 °C