This is a Compact NS1600N circuit breaker basic frame, 1600A, 50kA at 415 VAC 50/60 Hz, 4 poles . It is adapted for fixed devices electrically operated, and it is an optimum choice for all standard applications. This basic frame is compatible with any type of trip unit which has to be ordered separately. It can be equipped with a variety of optional functions and accessories. The dimensions are 327mm (W) x 280mm (H) x 147mm (D). It ensures compliance with international standards (IEC 60947), CCC, EAC and marine specifications.

Specification:

Main
Range ComPacT
Range of product ComPacT NS630b…1600 new generation
Device short name Compact NS1600N
Product or component type Basic frame
Device application Distribution
Number of poles 4P
Neutral position Left
[In] rated current 1600 A at 50 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN/IEC 60947-2
Utilisation category Category B
[Icu] rated ultimate short-circuit breaking capacity 50 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Performance level N 50 kA 415 V AC
control type Electrically operated
Mounting mode Fixed
Complementary
[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity 37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
[Icw] rated short-time withstand current 19.2 kA 1 s conforming to IEC 60947-2
Integral instant protection 40 kA
Mechanical durability 10000 cycles conforming to IEC 60947-2
Electrical durability 5000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
1000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
2000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
2000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Power losses 74 W
Mounting support Backplate
Connection pitch 70 mm
Protection type Without protection
Height (H) 327 mm
Width (W) 280 mm
Depth (D) 147 mm
Environment
Standards IEC 60947-2
Product certifications ASTA
ASEFA
LCIE
Pollution degree 3 conforming to IEC 60947
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to EN 50102
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -50…85 °C