Micrologic 5.0 is an electronic trip unit used on Compact NS630b to NS3200 circuit breakers. This control unit has a selective protection and is designed to protect power circuits and loads. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 5.0 indicates overloads with an Alarm LED. This trip unit can be associated with Compact NS basic frame.

Range ComPacT
Range of product ComPacT NS630b…1600 new generation
Product or component type Trip unit
Trip unit name MicroLogic 5.0
Trip unit technology Electronic
Range compatibility ComPacT new generation NS630b…1600
Device application Distribution
Number of poles 4P
3P
Protected poles description 3t
3t + N/2
4t
Trip unit protection functions Selective protection
Protection type for short time short-circuit protection
for overload protection (long time)
for instantaneous short-circuit protection
Trip unit rating 630 A at 50 °C
800 A at 50 °C
1000 A at 50 °C
1250 A at 50 °C
1600 A at 50 °C
2000 A at 50 °C
2500 A at 50 °C
3200 A at 50 °C
network type AC
Network frequency 50/60 Hz
Circuit breaker mounting mode Drawout
Fixed
Complementary
Long-time pick-up adjustment type Ir (thermal protection) Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range 0.4…1 x In
Long-time protection delay adjustment type tr Adjustable 9 settings
[tr] long-time protection delay adjustment range 0.7…16.6 s at 7.2 x Ir
0.5…24 s at 6 x Ir
12.5…600 s at 1.5 x Ir
Thermal memory 20 mn
Short-time protection pick-up adjustment type Isd Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range 1.5…10 x Ir
Short-time protection delay adjustment type tsd Adjustable
[tsd] Short-time protection delay adjustment range 0…0.4 s I²t=off
0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type Ii Adjustable 9 settings
[Ii] instantaneous protection pick-up adjustment range 2…15 x In
Off
Earth-leakage protection Without
Zone selective interlocking ZSI Without
Local signalling 3 LEDs (red) for electrical fault
1 LED (red) for internal error
Environment
ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -50…85 °C