Home
Shop

Schneider Electric Switch-disconnector Compact INS125 – 4 poles – 125 A

Part Number:

28911

This Compact INS125 is a 4 poles non-automatic switch-disconnector with black rotary handle. It is suitable for isolation with positive contact indication, as defined by IEC 60947-1 and IEC60947-3 standards. The operational current is 125A at 415VAC in categories AC22A and AC23A. The rated voltage is 690VAC 50/60Hz or 250VDC. The black rotary handle is designed to offer easy operation and high performance in interruption of currents. Compact INS125 is a class II insulation level front-face device as per IEC 60664 standard.

Specification:

Main
Range ComPact
product name ComPacT INS
Product or component type Switch disconnector
Poles description 4P
Network type AC
DC
Network frequency 50/60 Hz
[Ie] rated operational current AC-22A: 125 A AC 50/60 Hz 220/240 V
AC-22A: 125 A AC 50/60 Hz 380/415 V
AC-22A: 125 A AC 50/60 Hz 440/480 V
AC-22A: 125 A AC 50/60 Hz 500 V
AC-22A: 125 A AC 50/60 Hz 660/690 V
AC-23A: 125 A AC 50/60 Hz 220/240 V
AC-23A: 125 A AC 50/60 Hz 380/415 V
AC-23A: 125 A AC 50/60 Hz 440/480 V
AC-23A: 125 A AC 50/60 Hz 500 V
AC-23A: 80 A AC 50/60 Hz 660/690 V
DC-22A: 125 A DC 125 V 2 poles in series
DC-23A: 125 A DC 125 V 2 poles in series
DC-22A: 125 A DC 250 V 4 poles in series
DC-23A: 125 A DC 250 V 4 poles in series
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
[Ith] conventional free air thermal current 125 A at 60 °C
[Icm] rated short-circuit making capacity 154 kA with upstream protection circuit breaker 690 V AC at 50/60 Hz
20 kA switch-disconnector alone 690 V AC at 50/60 Hz
[Ue] rated operational voltage 250 V DC
690 V AC 50/60 Hz
Suitability for isolation Yes
Contact position indicator Yes
Visible break No
Pollution degree 3
Complementary
control type Rotary handle
Handle colour Black
Mounting mode Fixed
Mounting support DIN rail
Plate
Upside connection Front
Downside connection Front
Maximum power AC-23: 55 kW at 440 V AC 50/60 Hz
AC-23: 37 kW at 220/240 V AC 50/60 Hz
AC-23: 55 kW at 380/415 V AC 50/60 Hz
AC-23: 75 kW at 500/525 V AC 50/60 Hz
AC-23: 75 kW at 660/690 V AC 50/60 Hz
Rated duty Uninterrupted
Intermittent duty class Class 120 – 60 %
[Icw] rated short-time withstand current 1 kA during 30 s conforming to IEC 60947-3
1.23 kA during 20 s conforming to IEC 60947-3
3.175 kA during 3 s conforming to IEC 60947-3
5.5 kA during 1 s conforming to IEC 60947-3
Mechanical durability 15000 cycles
Electrical durability AC-22A: 1500 cycles 220/240 V AC 50/60 Hz
AC-22A: 1500 cycles 380/415 V AC 50/60 Hz
AC-22A: 1500 cycles 440 V AC 50/60 Hz
AC-22A: 1500 cycles 500 V AC 50/60 Hz
AC-23A: 1500 cycles 220/240 V AC 50/60 Hz
AC-23A: 1500 cycles 380/415 V AC 50/60 Hz
AC-23A: 1500 cycles 440 V AC 50/60 Hz
AC-23A: 1500 cycles 500 V AC 50/60 Hz
DC-22A: 1500 cycles 250 V DC 4 poles in series
DC-23A: 1500 cycles 250 V DC 4 poles in series
AC-22A: 1500 cycles 690 V AC 50/60 Hz
AC-23A: 1500 cycles 690 V AC 50/60 Hz
Connection pitch 30 mm
Height 100 mm
Width 135 mm
Depth 62.5 mm
Net weight 0.9 kg
Environment
Standards IEC 60947-3
IEC 60947-1
Product certifications CCC
KEMA-KEUR
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to EN 50102
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -50…85 °C