Home
Shop

Schneider Electric Easy Pact MVS CB 1600A 50kA 3P MDO ETA5 Drawout Manual Circuit Breaker

Part Number:

MVS16N3MW5A

  • Outstanding durability with the features you need
  • Easy to order and stock
  • High quality: using advanced manufacturing methods and premium materials
  • Modular design helps to increase the shop floor efficiency, enables faster delivery of switch boards
  • Answers to the most stringent application with most reliable distribution systems ensuring continuity of service

EasyPact MVS16N is a 1600A circuit breaker. The breaking capacity (Icu) is 50kA rms at 440VAC 50/60Hz. The operational voltage is 690VAC. This version is 3 poles drawout. Electronic trip unit provides LSI protection include Overload, Short-time and Instantaneous protection. A digital LCD screen continuously displaysI1, I2, I3, IN and maximeter(Imax). Fault indications LED indicate 4 types of fault which are Ir (Overload), Isd (Short time), Ii (Instantaneous) and Ap (Internal fault). It could be manual operated without gear motor, closing release and opening release. EasyPact MVS is compliant with international standards (IEC 60947, CE, EAC and RoHS). The dimension is 439mm x 441mm x 395mm (H x W x D).

Range EasyPact
product name MVS16N
Device short name MVS16N
Product or component type Circuit breaker
Device application Distribution
Poles description 3P
Protected poles description 3P 3d
[In] rated current 1600 A at 40 °C
network type AC
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code N
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category B
Trip unit name ETA5S
Trip unit technology Electronic
Trip unit rating 1600 A
Complementary
Network frequency 50/60 Hz
control type Manually operated
Mounting mode Drawout
Mounting support Rail
Base plate
Connection position Vertical
Horizontal
Location of connection Rear
[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2
Circuit breaker CT rating 1600 A
Breaking capacity 50 kA Icu at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 50 kA (Ics) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 20000 cycles (with maintenance) conforming to IEC 60947-2
10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Connection pitch 115 mm without spreader
Contact position indicator Yes
[Icm] rated short-circuit making capacity 105 kA (Icm) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current 50 kA (1 s) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit protection functions LSI
Protection type Overload protection (long time)
Short time short-circuit protection
Instantaneous short-circuit protection
Fault indication Internal fault
Short-circuit
Overload
Long time pick-up adjustment type Ir Adjustable 9 settings
Long time pick-up adjustment range 0.4…1 x In
Long time delay adjustment type Adjustable 9 settings
[tr] long-time delay adjustment range 0.5…24 s at 6 x Ir
Short-time pick-up adjustment type Isd Adjustable 9 settings
[Isd] short-time pick-up adjustment range 1.5…10 x Ir
Short-time delay adjustment type Adjustable 5 settings
[tsd] short-time delay adjustment range 100…400 ms
Instantaneous pick-up adjustment type Ii Adjustable 9 settings
Instantaneous pick-up adjustment range Off
2…15 x In
Zone selective interlocking ZSI With
Display type Digital display
Type of measurement Current
Current sensor rating range 400/2000 A
Maximum breaking time 25 ms
Maximum closing response time 70 ms
Height 439 mm
Width 441 mm
Depth 395 mm
Net weight 70 kg
Environment
Standards IEC 60947-2
Product certifications IEC
CCS
CCC
GOST
Pollution degree 4 conforming to IEC 60664-1
IP degree of protection IP40
ambient air temperature for operation -5…70 °C
Ambient air temperature for storage -40…85 °C without control unit
-25…85 °C with control unit